化工进展 ›› 2017, Vol. 36 ›› Issue (01): 100-106.DOI: 10.16085/j.issn.1000-6613.2017.01.013

• 化工过程与装备 • 上一篇    下一篇

R32制冷系统湿压缩的最佳吸气干度范围

王超, 陶乐仁, 黄理浩, 虞中旸, 沈冰洁   

  1. 上海理工大学能源与动力工程学院制冷与低温研究所, 上海 200093
  • 收稿日期:2016-05-16 修回日期:2016-06-24 出版日期:2017-01-05 发布日期:2017-01-05
  • 通讯作者: 陶乐仁,教授,研究方向为制冷及低温技术。E-mail:cryo307@usst.edu.cn。
  • 作者简介:王超(1990-),男,硕士研究生,研究方向为制冷系统优化。
  • 基金资助:
    上海市动力工程多相流动与传热重点实验室(1N-15-301-101)项目。

The optimal of suction refrigerant quality for R32 wet compression refrigeration system

WANG Chao, TAO Leren, HUANG Lihao, YU Zhongyang, SHEN Binjie   

  1. Institute of Refrigeration and Cryogenies, School of Energy and Power Engineering, University of Shanghai for Science and Technology, Shanghai 200093, China
  • Received:2016-05-16 Revised:2016-06-24 Online:2017-01-05 Published:2017-01-05

摘要: 湿压缩应用于R32制冷系统时能有效降低压缩机排气温度,但是其对系统性能的影响有待研究。在热力循环理论计算分析的基础上,利用变频滚动转子式压缩机制冷循环实验台,通过改变压缩机频率和电子膨胀阀的开度做了一系列实验,研究不同工况下R32制冷系统各项参数的变化趋势,寻找系统最优时吸气干度范围。理论分析表明:吸气带液时系统的性能比吸气过热时要好;从吸气过热到吸气带液,排气温度快速降低,而制冷量和COP先升高后降低,压缩机吸气干度在0.90~0.93内,理论COP存在最大值。实验分析表明:吸气干度在0.96~1.0范围内,制冷量比常规应用中控制过热度5℃时的高5%~10%;排气温度比吸气过热度5℃时的排气温度低8%~16%;COP比吸气过热度5℃时的高5%~8%;系统压比降低,系统性能达到最优。

关键词: 热力学, 压缩机, 湿压缩, 系统性能, 优化

Abstract: Wet compression used in R32 refrigeration system can reduce compressor discharge temperature effectively,but its impacts on system performance need more studies. Based on the theoretical analysis of cycle thermodynamic calculation,this paper studies the variation trends of R32 refrigeration system parameters under different operating conditions for seeking the optimal of suction refrigerant. Utilizing the frequency conversion rolling rotor compression refrigeration cycle test bench,a series of experiments were done by changing the electronic expansion valve and compressor's frequency. Theoretical analysis shows that,when compressor sucks vapor-liquid mixed refrigerant,the system shows better performance than that with superheat suction refrigerant;when the suction refrigerant transforms from superheating vapor to two-phase flow with little liquid,the discharge temperature rapidly reduces,cooling capacity and COP increase firstly and then decrease. When compressor suction refrigerant quality ranges from 0.90 to 0.93,the theoretical maximum COP exists. Experimental results showed that,when the suction refrigerant quality ranged from 0.96 to 1.0,cooling capacity was improved by 5%-10% over conventional refrigeration applications that the control superheat degree was at 5℃. Meanwhile,the discharge temperature decreased by 8%-16%,COP increased about 5%-8%,and system pressure ratio was decreased,and system performance reached the optimum state.

Key words: thermodynamics, compressor, wet compression, system performance, optimization