化工进展

• 化工过程与装备 • 上一篇    下一篇

不同外径组合转子过渡区强化传热性能实验研究

周寅鹏1,关昌峰1,张 震1,阎 华1,丁玉梅1,杨卫民1,2,于雁飞3   

  1. 1北京化工大学机电工程学院,北京 100029;2北京化工大学有机无机复合材料国家重点实验室,北京 100029;3中国石化集团股份有限公司管道储运分公司聊城输油处,山东 聊城252000
  • 出版日期:2013-07-05 发布日期:2013-07-05

Experimental study on heat transfer enhancement performance of rotor-assembled strands with different diameters in transition region

ZHOU Yinpeng1,GUAN Changfeng1,ZHANG Zhen1,YAN Hua1,DING Yumei1,YANG Weimin1,2,YU Yanfei3   

  1. 1 College of Mechanical and Electrical Engineering,Beijing University of Chemical Technology,Beijing 100029,China;2State Key Laboratory of Organic-Inorganic Composites,Beijing University of Chemical Technology,Beijing 100029,China;Liaocheng Oil Transportation Department,Sinopec PSTC,Liaocheng 252000,Shandong,China
  • Online:2013-07-05 Published:2013-07-05

摘要: 以60%甘油水溶液为管程介质,对内置螺旋开槽两叶片转子换热管过渡区内的强化传热综合性能进行了实验研究。在雷诺数范围为2800~6200之间对光管性能进行了实验验证,以保证实验结果的可靠性。同时,对比分析了转子外径对其强化传热性能的影响,研究结果表明:内置转子强化管的努塞尔数Nu较光管约提高了60%~200%,阻力系数较光管约增大了16%~32%,综合评价因子PEC值介于1.56~2.79之间。此外,内置转子强化管的努塞尔数、阻力系数以及PEC值均随着转子外径的增大而增加,这是由于较大的转子外径使得转子具有更强的扰流与减薄边界层的作用。

关键词: 关键词:组合式转子, 外径, 强化传热, 阻力系数, 组合式转子, 外径, 强化传热, 阻力系数

Abstract: This research focused on the investigation of comprehensive heat transfer enhancement performances of the tube inserted with helical blade rotors with grooves. A 60% Glycerin solution was used as tube-side working fluid in transition region. In order to ensure the reliability of the experimental results,plain tube validation experiments were carried out with the Reynolds numbers ranging from 2800 to 6200. Meanwhile,the effects of rotor diameters on heat transfer enhancement performance of the rotors were investigated. The results showed that the Nusselt number of the rotors inserted tube was about 60%—200% higher than that of the plain tube under the same Reynolds numbers condition;the friction factor of the rotors inserted tube was about 16%—32% higher than that of the plain tube;the PEC values were obtained between 1.56 and 2.79. In addition,the Nusselt number,friction factor and PEC values of the rotors inserted tube increased with the increasing rotor diameter. This was because larger diameters of the rotors contribute to a stronger effect of swirling and thinning the boundary layer.

Key words: Key Words: rotors-assembled, diameter, heat transfer enhancement, friction factor, rotors-assembled, diameter, heat transfer enhancement, friction factor

京ICP备12046843号-2;京公网安备 11010102001994号
版权所有 © 《化工进展》编辑部
地址:北京市东城区青年湖南街13号 邮编:100011
电子信箱:hgjz@cip.com.cn
本系统由北京玛格泰克科技发展有限公司设计开发 技术支持:support@magtech.com.cn